How to test a level switch: a five-minute function check
A level switch that has not tripped for months may still be working, or it may not. With a mechanical diaphragm switch you can find out in a few minutes, by hand, without filling the silo.
Before you start
Agree with whoever runs the plant that you are testing. The test should stop a conveyor or raise an alarm, so make sure that does not cause a problem elsewhere.
Five steps
- Look at the diaphragm. It should be whole, without cracks, and free to move. A thin coating is fine. A hard crust that locks the diaphragm is not.
- Press the diaphragm. Press the centre firmly with your hand. You should feel a clear end stop after a few millimetres; the travel is limited to 3–4 mm.
- Check the contact. With a multimeter on the terminals, or by watching the PLC input, confirm that the contact changes over when you press and returns when you release.
- Check the action. Confirm that the right thing happens in the plant: the conveyor stops, the alarm sounds or the signal reaches the control room.
- Check the air filter or compensation diaphragm. On NV14P and NV10P, check that the air filter is not clogged. On the KM versions, check that the compensation diaphragm is intact.
How often
Test before each season, for example before harvest or before the heating season, and after any work on the silo or conveyor. Where the switch protects against overfilling, many plants include it in their regular safety checks.
If it fails
If the contact does not change over, check the cable and terminals first. If the diaphragm is damaged or the switch does not respond, replace it. All four Elniva models are in stock in Stockholm and ship within 1–2 working days.